Products Services References Knowledge base About Contact
PL EN DE
Solplanet · Inverters

Solplanet ASW H-T3 DG (PRO)

Three-phase hybrid inverter with generator support

AC power8-12 kW
Phases3-phase
MPPT3
GeneratorYes
ProtectionIP66

Three-phase Solplanet H-T3 DG series hybrid inverters, 8-12 kW, with diesel generator support - they work with a 3-phase generator even without an autostart function and can control a heater (input / output). Three independent MPPT inputs, high-voltage Ai-HB batteries (120-600 V), UPS/EPS backup with switching time below 10 ms and an IP66 rating for outdoor mounting. Up to 150% PV oversizing and 50 A max charge/discharge current.

Models

Three models 8-12 kW.

Match the inverter power to the size of the installation. All H-T3 DG models have 3 MPPT inputs, 3-phase generator support, 50 A max charge/discharge current and IP66 protection.

ParameterASW08kH-T3-DGASW10kH-T3-DGASW12kH-T3-DG
Rated AC power8000 VA10000 VA12000 VA
Max. PV array power12000 Wp15000 Wp18000 Wp
Rated output current (@400V)11.6 A14.5 A17.4 A
Max. output current (@400V)12.8 A16.0 A19.2 A
Max. charging / discharging power8000 W10000 W12000 W
Max. input power from grid16000 W20000 W24000 W
Max. apparent power for generator12000 VA15000 VA18000 VA
Euro / max. efficiency97.2% / 98.0%97.9% / 98.4%97.9% / 98.4%
Capabilities

Key features.

Generator operation
Works with a 3-phase generator even without an autostart function.
Heater control
Input / output to control a heater - additional use of energy.
3x MPPT
Three MPPT trackers for difficult roofs and extensive strings.
AC coupling
Expand the installation with storage on an inverter from any manufacturer.
Off-grid installations
Ideal for sites with backup power and island operation.
Ai-HB batteries
Works with Solplanet high-voltage energy storage.
Technical data

Specification.

Parameters shared across the entire ASW H-T3 DG series. Values that differ between models are in the comparison table above.

Inverter typeHybrid, 3-phase (DG series)
Max. DC voltage1100 V
MPPT voltage range150-950 V
Start / rated input voltage180 V / 630 V
MPPT / strings3 / 1 per MPPT
Max. current per MPPT16 A
Max. short-circuit current per MPPT24 A
BatteryLiFePO4, high-voltage (Ai-HB)
Battery voltage range120-600 V
Max. charging / discharging current50 A
Max. charging power from PV and grid12000 W
Rated grid voltage3/N/PE, 230 V / 400 V
AC voltage range270-480 V
EPS / UPS switching time< 10 ms
Max. efficiency / MPPT98.4% / 99.9%
Generator input (GEN)3/N/PE, 230 V / 400 V
Heater / load control2 outputs / 4 inputs (dry contact)
CommunicationWiFi / LAN / Ethernet, CAN, RS485, Modbus RTU/TCP
Dimensions (W/H/D)625 / 465 / 241 mm
Weight29.5 kg
Operating temperature range-25 to +60 °C
CoolingNatural convection
Protection ratingIP66 (outdoor use)
ProtectionsDC SPD (Type II), AFCI, RCMU, ground fault, anti-islanding
Downloads

Documentation.

Product photos are coming soon. Need more documents? Get in touch or email handel@mplenergy.pl.

Ask about the ASW H-T3 DG (PRO).

We will help you choose, and prepare an offer and terms for installers and B2B partners.